Protection against Electric Field in the Outdoor Switch-Gear Workplaces
DOI:
https://doi.org/10.5755/j01.eee.112.6.435Abstract
The technique of the electric field distribution analysis in the 330 kV outdoor switch-gear is proposed. There are the zones in which electric field strength is greater than maximum permissible values by European Directive 2004/40/EU. The peak values of electric field strength are under the wires of A and C phases. These results are confirmed using programme package COMSOL. The electric field strength can be diminished to permissible values by shielding. It can be used as a shield comprised of some metal bars mounted parallel to wires of A and C phases over the shielding place. For the purpose of shielding it is sufficient to mount two bars provided they are mounted in the height of at least 2,4 m. Ill. 5, bibl. 4, tabl. 1 (in English; abstracts in English and Lithuanian).Downloads
Published
2011-06-08
How to Cite
Deltuva, R., & Virbalis, J. A. (2011). Protection against Electric Field in the Outdoor Switch-Gear Workplaces. Elektronika Ir Elektrotechnika, 112(6), 11-14. https://doi.org/10.5755/j01.eee.112.6.435
Issue
Section
ELECTRICAL ENGINEERING
License
The copyright for the paper in this journal is retained by the author(s) with the first publication right granted to the journal. The authors agree to the Creative Commons Attribution 4.0 (CC BY 4.0) agreement under which the paper in the Journal is licensed.