Performance of Linear Electric Drive at Localizing of Dust Explosions
DOI:
https://doi.org/10.5755/j01.eee.122.6.1831Abstract
Performance of dust explosion localizing systems with fire blocking dampers, whose moving element is aligned with linear induction motor (LIM) secondary element, is considered. It is stated experimentally, that dust explosion wave can deform moving element and it will begin to graze LIM inductor and could be lost control of ADELS. Therefore additional sliding and rolling bearings should be mounted in the active zone of LIM; sliding index of those differs from that of damper directives. Simulation of linear induction drive with load, depending on dust explosion pressure and degree of deformation of damper moving element with indicated capability of damper with the additional bearings in LIM active zone to block even strong primary explosion sources. Ill. 7, bibl. 5 (in English; abstracts in English and Lithuanian).Downloads
Published
2012-06-07
How to Cite
Rinkeviciene, R., Savickiene, Z., & Poska, A. J. (2012). Performance of Linear Electric Drive at Localizing of Dust Explosions. Elektronika Ir Elektrotechnika, 122(6), 100-104. https://doi.org/10.5755/j01.eee.122.6.1831
Issue
Section
ELECTRICAL ENGINEERING
License
The copyright for the paper in this journal is retained by the author(s) with the first publication right granted to the journal. The authors agree to the Creative Commons Attribution 4.0 (CC BY 4.0) agreement under which the paper in the Journal is licensed.
By virtue of their appearance in this open access journal, papers are free to use with proper attribution in educational and other non-commercial settings with an acknowledgement of the initial publication in the journal.