Practical Assessment of Synchronous Generator Dynamic Model Parameters

Authors

  • M. Ažubalis Kaunas University of Technology
  • V. Ažubalis Kaunas University of Technology
  • A. Jonaitis Kaunas University of Technology

Abstract

The paper presents analysis of evaluation methods of synchronous generator dynamic model parameters according to field test data. The list of parameters of the dynamic model for analysis of electromechanical transient processes and stability conditions in power systems is presented. The parameters of direct and quadrature axes can be evaluated according to frequency response test applied to the stopped generator. Regime tests of operating generator can be used for evaluation of direct axis parameters as well as for value of inertia constant. The open circuit characteristic is used for assessment of saturation characteristic. The methodic of parameters’ evaluation is created and equations for their evaluation according to field test data are presented.

Downloads

Published

2010-11-19

How to Cite

Ažubalis, M., Ažubalis, V., & Jonaitis, A. (2010). Practical Assessment of Synchronous Generator Dynamic Model Parameters. Elektronika Ir Elektrotechnika, 106(10), 33-36. Retrieved from https://eejournal.ktu.lt/index.php/elt/article/view/9113

Issue

Section

ELECTRICAL ENGINEERING